91000 Series Temperature Regulator
The “Self-Op” (Self-Operated Temperature Regulator)


foto producto

Description:

  • Self-Operating Design
  • Indicating, Non Indicating or Safety Models Available
  • Heavy Duty Die Cast Aluminum Housing
  • 1/2" thru 6" Valve Sizes
  • Fully Enclosed Bellows
  • Internal Overrange protection

The 91000 Series (Models 91000, 91400 & 91600) Self-Operating Temperature Regulator is the preferred choice of original equipment manufacturers, mechanical contractors and specifying engineers. These regulators require no external power source and are ideal for regulating the temperature of tanks, process streams and various types of industrial equipment. The Actutator is noted for its rugged die-cast aluminum housing, fully enclosed bellows assembly and internal over range protection.

Valve bodies for the 91000 are offered in singleseated, double-seated and 3-way designs and are available in Bronze, Cast-Iron, Cast-Steel and Stainless Steel construction.

The Model 91000 (without indicating dial) features a lower profile and should be specified where space constraints may be an issue.

The Model 91400 (with indicating dial) will allow the operator to verify the process temperature and to aid in temperature adjustment.

The Model 91600 Fail-Safe Actuator is designed to cause the valve to fail in the safe control position (open in a cooling application, closed in a heating application) should accidental damage to the thermal system occur, resulting in loss of the pressure charge.

For optimal performance, the service conditions (medium, flow, temperature, inlet and outlet pressures) of the application must be considered when selecting a valve. Please refer to the Valve Selection Section of this catalog. For applications where the process media may be corrosive or contained under pressure, the use of a thermowell is required to prevent damage to the regulator bulb and facilitate its removal from the process. Improper application may cause failure of the valve, resulting in possible personal injury or property damage.


Specifications:

Actuator Models: 91000 (Non-Indicating) 91400 (Indicating Dial) 91600 (Fail-Safe)
Power Requirements: Fully self-contained – no external power required
Dial Thermometer: 31/2" dial, stainless steel case, swivel and angle adjustment (Model 91400 only)
Housing: Die cast aluminum, epoxy powder coated blue finish
Set Point Scale: Integral to housing
Bellows: High pressure brass, corrosion resistant, tin plated finish
Adjustment Screw: Brass
Adjustment Screw Bushing: Lubricant impregnated sintered bronze
Range Adjustment Spring: Cadmium Plated
Overrange Protection: Upper range limit +100°F for temporary situations (not available for Model 91600)
Approximate Shipping Weight: Actuator model 91000: 6.0 lbs [2.70 kg] Actuator model 91400: 6.6 lbs [2.97 kg] Actuator model 91600: 9.5 lbs [4.32 kg]
Valve: See Valve Selection tables

Dimensions:

curvas

curvas

curvas


Standard ranges:

91000 & 91400 Actuators
Range Code Nominal Range Recommended Working Span Dial Thermometer Range
(Model 91400 only)
Single Seat, In-To-Close Valves
Double Seat, In-To-Close Valves
Double Seat, In-To-Open Valves
All 3-Way Valves
Single Seat
In-To-Open Valves
R01* 20° to 70°F & -10° to 20°C 40° to 65°F & 5° to 20°C N/A 30° to 115°F & C
R02* 40° to 90°F & 5° to 30°C 65° to 85°F & 20° to 30°C N/A 50° to 140°F & C
R03 30° to 115°F & 0° to 45°C 85° to 110°F & 30° to 45°C 50° to 80°F & 10° to 25°C 30° to 115°F & C
R04 50° to 140°F & 10° to 60°C 110° to 135°F & 45° to 60°C 80° to 105°F & 25° to 45°C 50° to 140°F & C
R05 75° to 165°F & 25° to 70°C 135° to 160°F & 60° to 70°C 105° to 130°F & 40° to 50°C 75° to 165°F & C
R06 105° to 195°F & 40° to 90°C 160° to 190°F & 70° to 90°C 130° to 155°F & 50° to 65°C 105° to 195°F & C
R07 125° to 215°F & 55° to 100°C 190° to 210°F & 90° to 100°C 155° to 180°F & 65° to 80°C 125° to 215°F & C
R09 155° to 250°F & 70° to 120°C 210° to 245°F & 100° to 120°C 180° to 215°F & 80° to 100°C 155° to 250°F & C
R10 200° to 280°F & 95° to 135°C 245° to 275°F & 120° to 135°C 215° to 245°F & 100° to 120°C 200° to 280°F & C
R11 225° to 315°F &110° to 155°C 275° to 310°F & 135° to 155°C 245° to 280°F & 120° to 140°C 225° to 315°F & C
R12 255° to 370°F &125° to 185°C 305° to 365°F & 155° to 185°C 275° to 335°F & 135° to 165°C 255° to 370°F & C
R13 295° to 420°F &145° to 215°C 365° to 415°F & 185° to 215°C 335° to 385°F & 165° to 195°C 295° to 420°F & C
R14 310° to 440°F &155° to 225°C 415° to 435°F & 215° to 225°C 385° to 405°F & 195° to 205°C 310° to 440°F & C

* Not recommended for single seated valves.

The recommended working span typically falls within the upper third of the nominal range. Single Seat In-To-Close, all Double Seat, and all 3-Way valves have a recommended working span in this part of the nominal range. However, due to differing thrust requirements, Single Seat In-To-Open valves have a recommended working span in the middle one-third of the nominal range.

91600 Fail-Safe Actuators
Range
Code
Nominal Range
and Recommended Working Span
R81
40° to 65°F & 5° to 20°C
R82
55° to 80°F & 15° to 25°C
R83
65° to 90°F & 20° to 30°C
R84
80° to 110°F & 25° to 40°C
R85
90° to 115°F & 30° to 45°C
R86
110° to 140°F & 40° to 60°C
R89
140° to 175°F & 60° to 80°C
R90
170° to 195°F & 80° to 90°C
R91
190° to 210°F & 85° to 100°C
R92
205° to 225°F & 95° to 105°C
R93
215° to 250°F & 100° to 120°C
R94
230° to 265°F & 110° to 130°C
R95
245° to 280°F & 120° to 135°C
R96
270° to 300°F & 135° to 150°C